真空断路器
当前位置: 首页 > 产品 > 真空断路器
HVD1-12

1General概述

    HVD1-12(VS1-12) type indoor AC HV vacuum circuit breaker (hereinafter referred to as circuit breaker) are suitable for 12kV air-insulated indoor switchgears, used as protection and control unit of power equipment of industrial& mining enterprise. Due to the super excellence, it is especially for location where requires the frequent operation of rated working current or multi breaking short circuit current.

     The circuit breaker adopts the integrated design of operating mechanism and circuit breaker body, servers as not only fixed installation, but also the handcart unit through equipping with a special propelling mechanism.

HVD1-12 has two main types. Draw-out type is HVD1-12D. Fixed type is HVD1-12F.

Phase distance 150mm , 210mm and 275mm.

Above choice all could be solid embedded type.

HVD1-12型户内交流高压真空断路器是用于12KV空气绝缘的户内开关设备,作为电网设备、工矿企业动力设备的保护和控制单元。由于真空断路器的优越性,尤其适用于要求额定工作电流下的频繁操作,或多次开断短路电流的场所。该断路器采用操作机构与断路器本体的一体式设计,即可以作为固定安装单元,也可以配用专用推进机构,组成手车单元使用。手车式型号为HVD1-12D, 固定式型号为HVD1-12F。行间距为:150mm210mm275mm

以上均可做固封极柱.

  

2. Service conditions

3.1 Environment temperature:-15℃~+40;

3.2 Environment humidity: Daily average relative humidity:95%, monthly average relative humidity:90%; Daily average saturated vapor pressure:2.2×10-3Mpa,monthly average saturated vapor pressure:1.8×10-3Mpa;

3.3 Altitude: Not exceed 1000m

3.4 Earthquake intensity: Not exceed 8 degree;

3.5 Service location: No water, flammable or explosive matter, chemical corrosive gas or drastic vibration.

 

 

1. Main specifications and technical parameters主要技术参数

NO.

Item项目

Unit单位

Parameter参数

1

Rated voltage额定电压

KV

12

2

Rate frequency额定频率

Hz

50

3

Rated lightning impulse withstand voltage(1min)额定雷电冲击耐受电压(1分钟)

KV

75

4

Rated short-time power frequency withstand voltage (1min)额定工频耐受电压(1分钟)

KV

42

5

Rated short-circuit breaking current额定短路开断电流

KA

20

25

31.5

40

6

Rated current额定电流

A

630 1000
1250

630 1000
1250 1600

1250 1600
2000 2500

1600 2000
2500 3150

7

Rated peak withstand current额定峰值耐受电流

KA

50

63

80

100

8

Rated short time withstand current额定短时耐受电流4S

KA

20

25

31.5

40

9

Rated short time making current(peak)额定短路关合电流峰值

KA

50

63

80

100

10

Power frequency withstand voltage of secondary circuit(1min)二次回路工频耐受电压(1分钟)

V

2000

11

Rated operation sequence额定操作顺序


Off-0.3s-On&Off-180s- On& Off
Off -180s- On& Off -180s- On& Off*

12

Rated breaking current of capacitor bank额定单个/背对背电容器组开断电流

A

630/400(40kA 800/400)

13

Opening time(rated voltage)分闸时间(额定电压)

ms

20~50

14

Closing time(rated voltage)合闸时间(额定电压)

ms

30~70

15

Rated short-circuit current breaking times额定短路电流开断次数

times

50(40kA 30)

16

Mechanical life机械寿命

times

30000

17

Rated opening/closing voltage额定分闸合闸操作电压

V

AC110, 220; DC110, 220

18

Rated voltage of energy-storage motor储能电机额定电压

V

AC110, 220; DC100, 220